The Apollo Series 65 smoke detector (often mistakenly called the “Series 60”) is a widely used addressable optical smoke sensor, part of Apollo’s Discovery and XP95 families, designed for fire alarm control panels in commercial and industrial buildings. It uses a light-scattering principle to detect smoke particles and communicates digitally with the control panel, allowing precise location of an alarm.
Background: Apollo and the Series 60/65 Name
Apollo Fire Detectors Ltd, a UK-based company founded in 1980, is one of the world’s largest manufacturers of fire detection devices. The “Series 60” is a common misnomer; the actual product line is the Series 65, introduced in the 1990s as a successor to the earlier Series 60 range. The Series 65 includes optical smoke detectors, heat detectors, and combined units, all designed to fit the same base and work with Apollo’s analogue-addressable protocol.
The confusion arises because many online listings and older manuals refer to “Series 60” as a generic term, and some control panels from the 1980s used Series 60 detectors. However, current Apollo products are Series 65 or the newer Discovery range. The Series 65 is still widely installed and supported, making it a common replacement part in existing systems.
How the Apollo Series 65 Optical Smoke Detector Works
The detector uses an obscuration chamber with an infrared LED and a photodiode. In normal conditions, the photodiode receives no light from the LED because a baffle blocks the direct path. When smoke enters the chamber, particles scatter the infrared light, and some of it reaches the photodiode, generating a signal. The detector’s firmware analyses the signal pattern to distinguish smoke from dust or steam, reducing false alarms.
Key technical features include:
- Addressable communication: Each detector has a unique address set by a rotary switch (1–127) or via software, allowing the panel to identify the exact device.
- Analogue value reporting: The detector sends a continuous smoke level reading, not just an alarm/no-alarm signal, enabling pre-alarm warnings and drift compensation.
- Remote indicator output: A terminal allows connection of an external LED for visibility in high-ceiling areas.
- Reversible head: The detector head can be rotated for easy cleaning or replacement without rewiring.
Choosing the Right Apollo Series 65 Detector
Selecting the correct model depends on your system’s compatibility and the environment. Apollo’s Series 65 range includes:
- Optical smoke detector (58000-600): Best for slow-burning, smouldering fires (e.g., electrical wiring, foam).
- Heat detector (58000-700): For kitchens, garages, or dusty areas where smoke detectors would false alarm.
- Combined optical/heat (58000-800): Provides both smoke and heat sensing, useful for areas with varying fire types.
Before purchasing, verify that your control panel supports Apollo’s XP95 or Discovery protocol; Series 65 is compatible with both, but you must match the detector’s protocol to the panel. Also check the base type: Series 65 uses a standard 4-inch base (e.g., 45681-200), which is not compatible with older Series 60 bases.
Common Problems and Maintenance
Users often report false alarms or detector faults. Typical issues include:
- Dust accumulation: Over time, dust enters the chamber, causing the detector to interpret it as smoke. Cleaning with a vacuum or compressed air (as per manufacturer guidance) restores performance.
- Drift compensation: The detector automatically adjusts its baseline to compensate for gradual dirt build-up, but if the drift exceeds a threshold, the panel shows a “dirty” or “maintenance” warning.
- Incorrect addressing: If two detectors share the same address, the panel may show a fault or duplicate device error.
- Wiring issues: Loose connections or incorrect polarity (though Series 65 is polarity-insensitive) can cause intermittent faults.
Routine testing with a smoke aerosol (e.g., Solo A1) is recommended annually, and the detector head should be replaced after 10 years of service, as per EN 54-2 standards.
Comparing Series 65 with Discovery and Other Brands
Apollo’s newer Discovery range (e.g., 58000-900) offers advanced features like multi-criteria sensing and adaptive algorithms, but it is not backward-compatible with Series 65 bases. If you are upgrading an existing system, you must replace both bases and detectors. In contrast, Series 65 is a mature, proven technology with a large installed base, making it a cost-effective choice for retrofits.
Compared to other manufacturers like Hochiki or System Sensor, Apollo’s Series 65 is known for its robust build and easy maintenance, but it lacks the wireless options of some modern detectors. For new installations, many engineers prefer Discovery for its improved false-alarm immunity, but Series 65 remains a reliable, cheaper alternative.
Cost and Availability
Prices vary by supplier and region. A new Series 65 optical smoke detector head typically costs between $15 and $30, with bases around $5–$10. Used or refurbished units are cheaper but may have unknown service history. Because the Series 65 is still in production, spares are readily available from fire safety distributors and online marketplaces. Always purchase from reputable suppliers to ensure genuine Apollo parts, as counterfeit detectors may not meet safety standards.
Safety and Compliance Considerations
In many jurisdictions, fire alarm systems must comply with standards such as EN 54 (Europe) or NFPA 72 (USA). Apollo Series 65 detectors are certified to EN 54-7 for smoke detectors and EN 54-5 for heat detectors, making them suitable for most commercial installations. However, local regulations may require specific spacing, placement, or maintenance schedules. Always consult a certified fire alarm engineer for installation and testing to ensure compliance and safety.
Frequently Asked Questions
Is the Apollo Series 60 the same as Series 65?
No. The Series 60 was an earlier generation, now obsolete. Series 65 is the current replacement, with improved electronics and compatibility with modern control panels. If you have a Series 60 base, you cannot fit a Series 65 detector without changing the base.
How do I reset an Apollo Series 65 smoke detector?
Resetting is done from the control panel. Press the reset/resound button on the panel to clear the alarm. The detector itself has no reset button; it automatically resets when power is removed and restored, but the panel must be reset to clear the alarm condition.
Can I use a Series 65 detector with a wireless system?
No. The Series 65 is a wired device. Apollo offers wireless detectors in the Discovery and Soteria ranges, which use radio communication instead of a physical loop.
What does the LED indicator on the detector mean?
A steady green LED indicates normal operation, a flashing red LED indicates an alarm condition, and a yellow LED (if present) indicates a fault or maintenance required. The exact behaviour depends on the panel configuration.
How often should I test my Apollo Series 65 detectors?
National standards (e.g., BS 5839) recommend that detectors be tested annually with a suitable test aerosol, and that a functional check is done after any system modification. Some organisations test more frequently, such as quarterly, depending on risk assessment.
Related