The Apollo Series 65A is a widely used addressable optical smoke detector, part of Apollo’s Discovery and Series 65 family, designed for fire alarm systems in commercial and industrial buildings. It uses a light-scattering principle to detect smoke particles and communicates with a compatible fire alarm control panel, typically via a two-wire loop.
Background and Place in the Apollo Range
Apollo Fire Detectors, a UK-based manufacturer, introduced the Series 65 range in the 1990s as a replacement for the earlier 60 series. The “65A” designation specifically refers to the addressable version of the optical (photoelectric) smoke detector, as opposed to the conventional (non-addressable) 65 model. The Series 65A is now largely superseded by the Discovery range, but it remains common in existing installations, particularly in Europe, Asia, and the Middle East. The detector is designed to fit into a standard Series 65 base, such as the 45681-200 or 45681-201, and communicates using Apollo’s proprietary protocol, which is not directly compatible with other manufacturers’ panels without an interface.
How the Optical Sensing Works
The Series 65A uses a pulsed infrared LED and a photodiode arranged in a chamber that excludes ambient light. When smoke enters the chamber, light from the LED scatters off smoke particles and reaches the photodiode, generating a signal that the detector interprets as an alarm condition. This method is particularly effective for slow-burning, smouldering fires that produce large visible particles (typically 0.3 to 10 micrometres), such as those from upholstery, wiring insulation, or paper. It is less responsive to fast, clean-burning fires that produce small particles or no visible smoke, which is why optical detectors are often paired with heat or ionisation detectors in multi-sensor systems.
Addressable vs. Conventional: What the “A” Means
The key difference between the Series 65 and 65A is communication. A conventional detector simply opens or closes a circuit, telling the panel only which zone (a group of detectors) has activated. The 65A, being addressable, has a unique digital address (set via a rotary switch on the detector or programmed in the panel) so the control panel knows exactly which device has triggered. This allows for faster pinpointing of a fire location, easier maintenance logging, and the ability to query each detector’s status (normal, alarm, fault, or pre-alarm) individually. The address is set using a small screwdriver on a dial with positions 1 to 128, and the detector must be addressed before installation, or the panel will report a duplicate or missing device fault.
Common Problems and Troubleshooting
- Dust contamination: Over time, dust enters the optical chamber and causes false alarms or drift. Apollo recommends cleaning with a vacuum or compressed air, but the detector should be replaced if internal contamination is severe.
- Address setting errors: If two detectors share the same address, the panel will show a fault or a “duplicate” error. Re-check the dial settings and the panel’s device map.
- Incompatible base or panel: The 65A only works with Series 65 bases and Apollo-compatible panels. Using a different base (e.g., a conventional one) will prevent proper seating or electrical contact.
- LED status not visible: The red LED on the detector blinks every few seconds in normal operation and latches on in alarm. If it never blinks, check the loop wiring and the address.
- High humidity or steam: Optical detectors can false-alarm in kitchens, showers, or boiler rooms. Apollo’s own documentation advises using a heat detector or a different sensor type in such areas.
How to Choose and Install Correctly
Selecting a Series 65A requires matching it to the environment and the panel. For most offices, corridors, and bedrooms, an optical detector is the default choice. For stairwells and escape routes, it is often used in combination with a heat detector. Installation steps are straightforward but must follow local fire codes and the panel manufacturer’s instructions:
- Confirm the control panel supports Apollo’s Series 65 protocol (not Discovery, which is a different protocol).
- Mount the base on a ceiling or wall, ensuring at least 500 mm clearance from walls and 300 mm from light fittings.
- Set the address dial on the detector to a unique number within the panel’s range.
- Twist the detector into the base until it clicks; the LED should blink once to confirm power.
- Commission the device from the panel, testing it with a proper smoke test aerosol or a magnet (Apollo’s test magnet activates the alarm without smoke).
Cost, Lifespan, and Replacement Considerations
As a discontinued product, new Series 65A detectors are increasingly hard to find, though used or refurbished units appear on secondary markets. Typical pricing for a new old-stock unit ranges from £15 to £30 (or $20–$40), while the base costs a few pounds more. However, the bigger cost is labour and system downtime. The detector’s expected service life is roughly 10 years from manufacture, after which the sensitivity can drift and internal components degrade. Many fire safety regulations now require detector replacement after 10 years, regardless of apparent function. If your system is older, upgrading to Apollo’s Discovery range (which uses the same base footprint for some models, but not the same protocol) may require a panel upgrade or a protocol converter, which is often more economical than maintaining obsolete hardware.
Safety and Testing Best Practices
Regular testing is mandatory in most jurisdictions. A functional test should be done at least annually, but many building managers do it quarterly. Use only approved smoke test aerosols (e.g., Solo or No Climb) or a magnet; never use an open flame, which can damage the detector and is a fire hazard. After a fire alarm test, reset the panel and check that the detector’s LED returns to normal blinking. If the detector goes into fault, clean it and re-test. Also, ensure that the detector is not painted or covered, as this blocks the smoke entry and voids the device’s certification. In high-dust environments, consider a remote test feature or a scheduled cleaning regime.
Frequently Asked Questions
Can I use a Series 65A with a conventional fire alarm panel? No. The 65A is an addressable device and requires a compatible addressable control panel. Using it with a conventional panel would require a zone monitor or an interface module, which is rarely practical.
What is the difference between the 65A and the 65 optical? The 65 is a conventional detector (two-wire, non-addressed), while the 65A is addressable. They look similar but are not interchangeable; the 65A has an address dial and uses a different communication protocol.
Is the Series 65A compatible with Apollo Discovery bases? No. Discovery bases use a different mechanical and electrical design. You must use Series 65 bases (e.g., 45681-200) for the 65A. Some third-party bases exist, but they are not certified by Apollo.
How do I clean a Series 65A detector? Remove the detector from its base, use a soft brush or vacuum to remove dust from the outer mesh, and gently blow out the optical chamber with compressed air. Do not use water, solvents, or lubricants, as they damage the electronics.
Why does my 65A keep giving false alarms? The most common causes are dust, insects, steam, or high humidity. Check the environment first. If the problem persists, test the detector with a magnet; if it alarms correctly, the issue is environmental, not the detector itself.
Can I replace the 65A with a Discovery detector without changing the base? Only if the base is a Series 65 base and you use a Discovery detector that is mechanically compatible (e.g., Discovery optical fits the same base). However, the panel must support Discovery protocol; otherwise, you need a panel upgrade or a protocol converter.