The Apollo S65 is a series of optical (photoelectric) smoke detectors manufactured by Apollo Fire Detectors Ltd, a UK-based company, designed for use in analogue-addressable fire alarm systems. These detectors use a scattered-light principle to sense smoke particles, making them particularly effective at detecting slow-burning, smouldering fires.
Background and Development
Apollo Fire Detectors introduced the S65 series in the late 1980s as a successor to their earlier 60-series detectors. The “S65” designation refers to the 65mm diameter of the detector base, which became a standard size for many Apollo detectors. The series was designed to be compatible with Apollo’s analogue-addressable control panels, which communicate with each detector individually over a two-wire loop. This allowed for more precise identification of the fire location and reduced false alarms compared to conventional systems. The S65 series was widely adopted in commercial and industrial buildings across Europe and other regions, and it remains in service in many installations today, despite being largely superseded by Apollo’s newer XP95 and Soteria ranges.
How the Optical Sensor Works
The S65 optical detector uses a light-scattering principle. Inside the detector chamber, there is a light-emitting diode (LED) and a photodiode (light sensor) positioned at an angle to each other. In normal conditions, the light from the LED does not directly reach the photodiode. When smoke enters the chamber, the smoke particles scatter the light, causing some of it to hit the photodiode. The detector then sends an analogue value to the control panel, which interprets the level of smoke and decides whether to trigger an alarm. This design is particularly sensitive to larger smoke particles produced by smouldering fires, such as those from overheated wiring or upholstery, but it is less sensitive to small, fast-flaming fire particles.
Key Features and Models
The S65 series includes several models tailored for different environments:
- Standard Optical Detector (ORB-OP-00001): The basic model for general use in offices, corridors, and retail spaces.
- Optical Heat Detector (ORB-OH-00001): Combines optical sensing with a thermistor to detect both smoke and rapid temperature rises, useful in areas with high humidity or steam.
- Optical with Remote LED (ORB-OP-00002): Includes a remote indicator output for visual alarm confirmation on high ceilings or in noisy areas.
- Harsh Environment Model: Designed with a sealed chamber and gaskets to resist dust, moisture, and insects, suitable for garages or warehouses.
- Marine Approved Model: Certified for use on ships and offshore platforms, with enhanced corrosion resistance.
Installation and Compatibility
The S65 detectors mount onto a standard Apollo base (e.g., the 45681-200 base). Wiring is a two-wire loop, which carries both power and data. The detector head twists and locks onto the base, and a small LED on the detector flashes to indicate its status. The S65 is compatible with Apollo’s intelligent control panels that support the S65 protocol, such as the XP95 and some older panels. However, it is not directly compatible with the newer Soteria range without an adaptor. Installation should be done by a qualified electrician or fire alarm engineer, following local codes and the manufacturer’s instructions. The detectors should be placed on ceilings at least 500mm from any wall, and at least 1m from air conditioning vents to avoid false alarms.
Common Problems and Troubleshooting
Like all smoke detectors, the S65 can experience issues:
- False alarms: Caused by steam, cooking fumes, or dust. Regular cleaning with a vacuum cleaner using a soft brush attachment can help.
- Detector not responding: Check the base wiring and ensure the detector head is fully locked in place. A faulty detector may need replacement.
- LED not flashing: This could indicate a loss of power or a fault. Verify the loop voltage and the detector’s address setting.
- Dirty chamber: Over time, dust can accumulate inside the optical chamber, causing nuisance alarms or reduced sensitivity. Some models have a removable chamber for cleaning, but if cleaning does not restore performance, replace the detector.
Cost and Availability
As of 2025, a new Apollo S65 optical detector head typically costs between £15 and £30 (or equivalent in other currencies), depending on the supplier and quantity. The base is usually sold separately for around £5 to £10. Because the S65 is an older series, it is becoming less common in new installations, but it is still available from specialist fire safety suppliers and online marketplaces. Used or refurbished units are also available, but for safety reasons, it is recommended to use new detectors from authorized distributors to ensure compliance with standards.
Comparison with Newer Apollo Detectors
Apollo has since released the XP95 series (which uses a similar protocol but with improved electronics) and the Soteria series (which uses a digital protocol and offers more advanced features like drift compensation and multi-criteria sensing). The S65 is generally less expensive but lacks the self-diagnostic features of newer models. For example, Soteria detectors can automatically adjust their sensitivity as they get dirty, reducing false alarms. If you are upgrading an existing S65 system, you may be able to use XP95 detectors with a compatible panel, but you should always check with the panel manufacturer for compatibility. For new installations, most engineers would recommend the Soteria range for its enhanced performance and longer service life.
Safety and Maintenance
Smoke detectors are life-safety devices, so regular testing and maintenance are essential. The British Standard BS 5839-1 recommends that detectors be tested annually by a competent person and cleaned as necessary. A simple test can be done using a can of smoke detector test aerosol (not actual smoke, which can contaminate the chamber). The detector should be tested after any building work, as dust can cause false alarms. Always replace a detector that has been painted over, as paint can block the smoke entry. The S65 has a nominal life of around 10 years, after which it should be replaced, as the sensor components degrade.
Frequently Asked Questions
Is the Apollo S65 compatible with my existing alarm panel?
It depends on your panel. The S65 uses Apollo’s analogue-addressable protocol, which is supported by many older Apollo panels (e.g., XP95, Discovery). Check the panel’s manual or consult a fire alarm engineer. If you have a conventional (non-addressable) system, the S65 will not work.
Can I replace an S65 detector with a newer model?
Yes, but you need to ensure compatibility. The XP95 series is often a drop-in replacement for S65 on compatible panels, but you must verify that your panel supports the XP95 protocol. The Soteria series requires a different base and panel compatibility, so it’s not a straightforward swap.
How do I know if an S65 detector is faulty?
If the detector’s LED is not flashing, or if it triggers false alarms frequently, it may be faulty. Use a test aerosol to see if it responds. If it doesn’t, or if it alarms without smoke, clean it first. If the problem persists, replace the detector head.
What is the difference between optical and ionisation smoke detectors?
Optical detectors (like the S65) are better at detecting slow, smouldering fires with large smoke particles. Ionisation detectors are more sensitive to fast-flaming fires with small particles. For most general applications, optical is preferred because it has fewer false alarms from cooking and steam.
Can I paint over the S65 detector?
No. Painting over any smoke detector will block the smoke entry holes and prevent it from sensing smoke, rendering it useless. If you must paint, remove the detector head and cover it, then replace it after painting.