The Apollo Series 65 smoke detector is a widely used conventional fire detection device, and its official data sheet is available from Apollo Fire Detectors as document number 25001 (for the optical model) and related numbers for variants. This guide explains what the data sheet contains, how the detector works, and how to interpret its specifications for real-world installation and maintenance.
What the Official Data Sheet Covers
The manufacturer’s data sheet for the Series 65 range lists mechanical dimensions, electrical ratings, environmental limits, and the detector’s response to standard fire test fires (EN 54-7). Key specifications include:
- Operating voltage: 8–33 V DC (typical systems run at 12 or 24 V)
- Quiescent current: approximately 45 µA at 24 V
- Alarm current: 16–70 mA depending on the base and supply
- Operating temperature: -20 °C to +60 °C
- Humidity: up to 95% relative humidity (non-condensing)
- Dimensions: 100 mm diameter, 42 mm height (with standard base)
- Weight: about 100 g (detector head only)
The data sheet also includes a wiring diagram for the standard 2-wire conventional connection, and a graph showing the detector’s sensitivity (obscuration) range, typically 0.5–1.5 dB/m for the optical model.
How the Series 65 Works
The Series 65 is a point-type smoke detector that uses a light-scattering (optical) principle. Inside the chamber, an infrared LED emits a pulsed beam; a photodiode sits at an angle so it only receives light when smoke particles enter and scatter the beam. When the scattered light exceeds a threshold, the detector goes into alarm. The chamber is designed with a labyrinth to block ambient light while allowing smoke to enter.
There are three main variants in the Series 65 range:
- Optical (model 55000-100) – best for slow, smouldering fires with large particles (e.g., overheated wiring, foam).
- Ionisation (model 55000-200) – uses a small radioactive source (Americium-241) to detect fast, flaming fires with small particles.
- Heat (model 55000-300) – responds to temperature rise, not smoke; used in kitchens or dusty areas.
The detector is conventional, meaning it does not report an address; it simply changes its current draw when in alarm. The control panel sees this as a zone alarm.
Choosing the Right Variant
Selecting between optical, ionisation, and heat depends on the environment and fire risk. For general living spaces, corridors, and offices, the optical version is the standard choice because it is less prone to false alarms from cooking fumes and steam. Ionisation detectors are more sensitive to invisible combustion products, but they are increasingly being phased out in many regions due to the radioactive source and disposal costs. Heat detectors are used in areas where smoke detectors would cause nuisance alarms, such as:
- Kitchens and canteens
- Boiler rooms
- Showers and saunas
- Dusty workshops
Check local fire codes; many require a specific type for certain rooms. For example, UK regulations (BS 5839-1) often recommend optical in circulation spaces and heat in kitchens.
Common Problems and Troubleshooting
Users frequently report false alarms or detectors that fail to test. The most common causes are:
- Dust accumulation in the optical chamber – clean with a vacuum or replace the head if it is over 10 years old.
- Incorrect base wiring – the Series 65 uses a 2-wire connection; reversing polarity prevents operation.
- Using the wrong base – the detector fits the standard Series 65 base (45681-200) or a relay base for remote indication.
- End-of-line resistor missing – this causes the panel to show a fault.
To test the detector, use a magnet or a dedicated aerosol smoke test (e.g., Solo A5). Do not use an open flame, as it can damage the chamber.
Comparison with Other Apollo Ranges
The Series 65 is an older conventional line, now largely superseded by the Discovery range (which is addressable) and the newer S65 series (which is a direct replacement with improved optics). Key differences:
- Series 65 vs. S65: The S65 has a more sensitive chamber and a different base pin layout; the S65 is not backward compatible with the old Series 65 base.
- Series 65 vs. Discovery: Discovery is addressable (each device has a unique ID), allowing the panel to pinpoint the exact detector. Series 65 only identifies a zone.
- Series 65 vs. XP95: XP95 is also addressable but uses a different communication protocol; it is common in industrial sites.
If you are extending an existing Series 65 loop, you must use the same type; mixing with S65 or XP95 will not work without a compatible interface.
Cost and Availability
As of 2025, a new Series 65 optical detector head typically retails for $15–$25 USD (or £10–£18 UK) depending on quantity and supplier. The base costs around $5–$10. However, because the range is being discontinued, prices may rise, and you may find surplus stock at lower prices. Genuine Apollo parts are widely available from fire safety distributors; avoid counterfeit units, which often fail to meet EN 54-7 standards.
For a full system, you also need a compatible conventional control panel (e.g., from Kentec, C-TEC, or Advanced) and a detector base. Installation should be done by a certified fire alarm engineer to comply with local codes.
Safety and Maintenance Requirements
Regular testing is essential. The data sheet recommends:
- Test every detector at least once a year (or as per local regulations).
- Clean the detector head every 3–6 months in dusty environments.
- Replace the detector after 10 years from date of manufacture, as the sensor degrades.
- Never paint the detector; paint blocks the smoke entry holes.
For ionisation models, disposal must follow local radioactive waste regulations – do not throw them in normal rubbish. Many suppliers offer a take-back scheme.
Frequently Asked Questions
Can I use a Series 65 detector with a wireless system? No, the Series 65 is a wired conventional detector. For wireless, Apollo offers the S65 wireless range, which uses a separate radio base.
How do I know if my detector is a Series 65 or S65? Look at the label on the back. The Series 65 has a model number starting with 55000; the S65 starts with 55000-600 (optical) or similar. Also, the S65 has a slightly different chamber shape.
Why does my detector keep beeping after I clean it? If the beeping continues, the detector may be faulty or the battery (if it is a combined smoke/CO unit) may be low. For wired models, a continuous beep usually indicates a fault – check the wiring and the end-of-line resistor.
Is the Series 65 ionisation detector safe? Yes, the radioactive source is sealed and poses no risk during normal operation. However, it must be disposed of properly, and some countries restrict new installations due to environmental concerns.
Can I replace a Series 65 with a different brand? Only if you also replace the base, because the pin layout and detection chamber are proprietary. It is simpler to stick with Apollo for that zone.
What does the data sheet’s ‘obscuration’ mean? It measures how much light is blocked by smoke. A higher value means the detector is less sensitive. The Series 65 optical is typically set to alarm at about 0.5 dB/m, which is a standard sensitivity for general areas.