The Apollo Series 65 optical smoke detector base is the mounting and wiring platform for the Series 65 range of detectors, providing the mechanical fixings, electrical connections, and optional remote indicator or relay functionality. It is not a detector itself; it is the component that connects the detector head to the fire alarm control panel and holds it securely in place.
Background: The Series 65 Range
The Apollo Series 65 is a long-established family of fire detectors introduced by Apollo Fire Detectors, a UK-based manufacturer. The range includes optical smoke detectors, ionisation smoke detectors, heat detectors, and multi-sensor detectors, all designed to fit onto a common base. The Series 65 has been widely installed across the world, particularly in commercial and industrial buildings, and remains a common sight in existing fire alarm systems. The optical variant, often referred to as the 65A or 55000-200 series, uses a light-scattering principle to detect smoke particles.
How the Base Works
The base is a simple but critical component. It has a circular plastic housing with terminals for connecting the detector to the fire alarm loop or zone wiring. The detector head twists and locks into the base, making electrical contact through metal pins. The base also provides a release mechanism—usually a small slot for a screwdriver—to unlock the head for maintenance or replacement.
There are several variants of the base, each with specific functions:
- Standard base (45681-200): The basic version, providing power and signal connections.
- Base with remote indicator (45681-211): Includes terminals for connecting an external LED, useful for areas where the detector is not visible, such as above a suspended ceiling.
- Base with relay (45681-213): Contains a relay that can be used to control auxiliary equipment, such as door closers or ventilation shutters.
- Base with sounder (45681-214): Incorporates a sounder to provide local audible alarm.
- Base with isolator (45681-220): Includes a short-circuit isolator, protecting the loop from a fault on a single device.
How to Choose the Right Base
Selecting the correct base is essential for system compatibility. The Series 65 bases are designed specifically for Series 65 detector heads; they are not interchangeable with other Apollo ranges such as the XP95 or Discovery. When choosing a base, consider:
- Detector type: Ensure the detector head (optical, heat, etc.) matches the base model.
- Wiring configuration: Check whether the system uses conventional (2-wire) or addressable (loop) wiring. Series 65 is primarily a conventional range, but addressable versions exist via the XP95 protocol.
- Additional functions: Decide if you need a remote indicator, relay, or isolator.
- Environmental rating: Standard bases are for indoor use; if the detector is exposed to moisture, you may need a weatherproof version or additional protection.
Installation and Wiring
Installation should be carried out by a qualified electrician or fire alarm engineer. The base is typically mounted on a ceiling or wall using screws through the fixing holes. Wiring is connected to the terminal blocks, which accept up to 2.5mm² cable. The detector head is then twisted into the base until it clicks.
A common question is whether the base can be used with other detector brands. The answer is no—the physical and electrical interface is proprietary to Apollo Series 65. Using a non-matching head could result in poor contact or false alarms.
Common Problems and Troubleshooting
Several issues can arise with Series 65 bases:
- Intermittent contact: This is often caused by a loose detector head or corroded terminals. Check that the head is fully locked and the terminals are tight.
- Remote indicator not working: Ensure the remote LED is wired to the correct terminals and the polarity is correct.
- Base not fitting: Some bases have a small alignment tab; if the head does not twist on, check that the tab is not broken.
- False alarms: While not directly a base issue, a dirty or faulty detector head can cause false alarms. The base should be kept clean and free from dust.
Comparison with Other Apollo Bases
Apollo offers several base families. The XP95 and Discovery bases are similar in concept but are not compatible with Series 65 heads. The main differences are in the communication protocol and the physical design. For example, Discovery bases have a more modern look and support a wider range of detectors, but they require a compatible control panel. Series 65 is often chosen for retrofits because it is widely available and cost-effective.
Cost and Availability
Series 65 bases are relatively inexpensive, typically costing a few pounds or dollars each, depending on the variant. They are widely available from fire safety suppliers and online retailers. However, as the range is older, some variants may be less common. It is always worth checking the manufacturer’s datasheet for the exact part number and specifications.
Safety and Maintenance
Fire alarm systems must be maintained in accordance with local regulations. Detectors and bases should be inspected regularly, cleaned, and tested. The base should be checked for physical damage, and the terminals for corrosion. When replacing a detector head, always isolate the circuit first to avoid electric shock. Also, ensure that the detector type matches the base—using an incompatible head could compromise fire detection.
Frequently Asked Questions
Can I use a Series 65 detector on a different base?
No. The Series 65 detector heads are designed to fit only on Series 65 bases. Using a different base may not provide a secure fit or correct electrical connection.
How do I remove a detector from the base?
Insert a small flat-head screwdriver into the release slot on the side of the base and gently lever while twisting the detector head counter-clockwise. The head should then lift off.
What does the remote indicator base do?
It allows you to connect an external LED that lights up when the detector goes into alarm. This is useful when the detector is hidden above a ceiling or in a dark area.
Is the Series 65 base compatible with addressable systems?
Yes, but only with addressable versions of the Series 65 detectors that use the XP95 protocol. The base itself is the same, but the detector head must be addressable.
Can I replace a Series 65 base with a newer Apollo base?
You can, but you would also need to replace the detector head and possibly the control panel, as newer bases are not backward compatible. It is usually simpler to stick with Series 65 if the rest of the system is intact.